Home Page News Search Contact Us Language Bar فارسی English
 
 
 
If you have faced with a case that needs conferring during your work or studies, you can submit it here as a "New Riddle" and we'll show it in your name. Notice: Site owners have the right to accept a riddle or not, or make a little changes in submited riddles.
Submit New Riddle

In one of the industrial site, the no earthed system has been chosen in electrical designing stage. Therefore nobody anticipated a strong earth fault current in the system.
Author : Hamid - From: Iran
 
According to IEEE 665 – section 5.5.3.1 page 27, it is important for the ground conductor to run as close as possible to the phase circuit conductors; since it will cause the fault current return path reactance to be reduced.
Author : Hamid
 
The electronic control systems in one power plant are digital base and separated "one point" grounding system is considered for it.
Author : Hamid
 
We have 25 earthing pits in telecom building these earthing pits conneted with each other with a lop could any one tel me in detail.
Author : maamir from pakistan
 
A design query on earthing trafo.
An earthing trafo installed on a 11 kv switchboard is rated for 381 kva , 11 kv/ 110v in a star - broken delta arrangement. A resistor rated 1.14 ohms is connected across the broken limb.
Author : Guest
 
Is there any potential hazard in bringing the neutral of several 11kV/400V Dyn11 transformers to a common earth bar and then connecting to the earth pits?
Author : Mohan
 
How to design a neutral grounding resistor for 5 MW generator and what are the points to be considered before design a NGR for generator? Kindly give some design methods or articles regarding this.
Author : T.Kailash Kumar
 
I was going through 11kV schemes.For every phase R,Y,B there is an individual Potential transformer for the outgoing feeder.
Author : GUEST
 
According to electrical basic design of one industrial plant, contractor shall supply suitable grounding transformer with an additional NGR in its neutral connection for limitation of ground fault current system to 400 A.
Author : Hamid - From: Iran
 
What is the origin of neutral bar voltage and how we can reduce it?
Author : Reza - From: IRAN
 
What is the advantage and disadvantage of combination of power transformers MV/LV grounding systems? Whether can we use the cable armor as grounding conductor in power system?
Author : SABA - From: IRAN
 
How can we choose the neutral wire size in various grounding system? Is there any guideline for non liner loads conditions?
Author : Ebrahim - From: IRAN
 
Recently we have carried out the periodic inspection in a manufacturing plant. This plant has a 6.6kv network supplying 3 remote buildings each with transformers. We found that the Zs readings throughout the installation in one of the buildings were high compared to previous inspection reports.
Author : Dale - From: England
 
We have a 11kV/400V 4MVA trafo with 97kA short ckt rating. Can u suggest for the neutral grounding methodology keeping high shrt ckt rating of the system
Author : san - From: INDIA
 
What consideration shall be taken in lightning protection grounding systems? Are there any estimation for lightning current surge?
Author : Hamed - From: Iran
 
i want to know how do u calculate the ohmic resistance value of ngr for transformer protection,say if i do provide u primary seconday voltage ,current of transformer.
Author : bipul pandey - From: india
 
In parallel operation of generators, Sometimes the neutral point of one of them is grounded and other not. Are there any technical reason for this operation way?

  
Author : Mohammed amin - From: Egypt
 
What is advantage and disadvantage of various grounding systems such as solidly, low impedance or high impedance grounding systems?
Author : Guest - From: Syria
 

What amount of grounding impedance shall be considered in grounding system planning stage?
Author : S.O - From: Turkey
 
Why do we ground positive terminal of electro-static-precipitator (ESP)?
Author : Yogi - From: India
 
Is there any technical guide for choosing  the best grounding system between IT,TT or TN systems?
Author : Reza - From: Iran
 
I urgently need the main earthing conductor sizing calculation of 132kV substation
Author : Asif - From: Abu dhabi
 
Is it possible to connect such a transformer solidly grounded ( 10/0.4 kv Dyn11 auxilary transformer ) in same grounding as individually high resistance grounded 10kV generator units?
Author : Guest
 
In my house we do not have access to earth, can we use neutral wire instead of earth electrode for grounding of metal enclose of electrical equipments?
Author : Javad
 
 
 
Change Language :